FD800 series
Rivelatori lineari autoallineanti serie FD800
Rivelatori lineari autoallineanti serie FD800
TruVision video management software
Encoder Truvision IP con 1, 2, 4 & 8 canali, codifica H.264 & H.265. Supporta la codifica delle telecamere analogiche ed HD-TVI TruVision fino a 5 o 8 megapixel in base al modello.
Decoder TruVision per 16 flussi video Full HD, 3 usctie (HDMI, VGA, BNC), 12 VDC
Tastiere TruVision IP/RS485 con joystick a 4 assi
Lettore USB ATS per acquisizione tessere Hitag2 e Mifare CSN
Inserire almeno 2 caratteri per avviare la ricerca.
Rivelatore ottico di fumo con buzzer e batteria.
Rivelatore ottico di fumo con buzzer e batteria.
The 562NSE is an EN14604 approved, battery powered, stand-alone smoke detector with built in sounder. It features a local silence and test function, as well as a field exchangeable optical chamber for ease of cleaning and maintenance. All detectors are shipped with a dust cover for protection on construction sites with dusty environments.
The 562NSE offers complete stand-alone applications with "peace-of-mind" functionality. An extended LED feature set and local test facilities allow the user total visibility of the functionality of the detector. When maintenance is required, both to the detector or the batteries, the user will be timely notified.
The LED on the detector indicates the status of the detector:
FLASHING: A flash every 9 seconds during normal operation
ON: Fire alarm
OFF: Trouble or maintenance required
The sensitivity of the device is indicated on the LED of the detector during detector maintenance testing.
The 560 series detectors may be tested on location using canned aerosol simulated smoke. The detector LED remains ON and the alarm sounds a temporal rhythm until the Test/Silence button is pressed. The detector automatically resets when smoke is no longer present. A local alarm indicates the end of any test sequence.
Sensitivity testing and contamination monitoring on the detector allows the detector to indicate when maintenance is required. For cleaning, simply exchange the optical chamber (211) on site. The detector automatically recalibrates meaning that no special tools are required.
Elettrico | |
---|---|
Tensione di esercizio | 3 VDC |
Fisico | |
---|---|
Dimensioni fisiche | 142 x 61 mm (Ø x H) (Detector) 137 x 117 mm (Ø x H) (Base) |
Colore | Bianco |
Ambientale | |
---|---|
Temperatura operativa | +4 to +38°C |
Temperatura di immagazzinamento | -34 to +60°C |
Umidità relativa | 90% max. noncondensing |
Ambiente | Interno |
Standard e norme | |
---|---|
Certificazioni | EN14604 |
Low battery threshold | |
---|---|
Low battery signal at 2.7V |
Batteries | |
---|---|
Battery life | 1 year (min) |
Battery type | 2 x 3 V lithium (Duracell® 123 or equivalent) |
Detector sensitivity | |
---|---|
0.14 ± 0.04 dB/m |
Drift compensation | |
---|---|
1.64%/m (0.5%/ft.) max. |
Curent consumption | |
---|---|
Stand by | 35 µA |
Alarm | 70 mA |
Test | 2 mA |
Sounder | |
---|---|
Alarm | 85 dB @ 3 m, temporal output |
Low battery | 1 every 45 ± 2 seconds |
Environmental | |
---|---|
RFI immunity | 10 V/m minimum; 0-1000 MHz |
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.